Refrigerant System Specifications

Refrigerant System Capacities

Application Specification
Metric English
PAG Oil-Refer to Adhesives, Fluids, Lubricants, and Sealers .
Compressor Replacement
NOTE:

Compressor failure can occur if the oil removed during refrigerant recovery is not replaced.

The service compressor is precharged with one of the following specified amounts of PAG oil. Refer to the instruction sheet included with the service compressor.
40 ml1 1.4 oz1
Condenser Replacement 20-25 ml1 0.7-0.88 oz1
Evaporator Replacement 15-20 ml1 0.53-0.7 oz1
  • Total System PAG Oil Capacity
70 ml 2.5 oz
R-134a
  • Refrigerant Charge
0.57 kg 1.26 lb
R-1234yf
  • Refrigerant Charge
0.62 kg 1.37 lb
1 If more than the specified amount of PAG oil was drained from a component, add the amount drained.