Procedure For Detection Of Refrigerant Leaks (ITB96-041)
Publication date: 1996-09-11Reference number: ITB96-041
Supersedes refnos: ITB95-004
PROCEDURE FOR DETECTION OF REFRIGERANT LEAKS
TECHNICAL SERVICE BULLETIN
REVISED PROCEDURE FOR DETECTION OF REFRIGERANT LEAKS
Model(s): All Infiniti Models
Classification: HA96-004
Section: Heater & Air Conditioner
Bulletin No.: ITB96-041
Date: September 11, 1996
SERVICE INFORMATION
An updated refrigerant leak detection procedure is now included in all service manuals beginning with the 1997 model year.
The revised procedure is applicable to all models and includes the following changes or additions:
- A minimum charge specification prior to conducting the leak check.
- The recommended minimum ambient temperature for effective leak detection.
- Recommended probe tip moving speed and position away from the point to be checked.
- Proper cleaning of A/C components and fittings prior to leak checking.
- Rechecking a suspected leak.
- Checking procedures for specific A/C components such as the compressor, liquid tank, service valves and cooling unit.
- Elimination of soap and water as a secondary check method.
In some cases you may not detect a leak readily if both the high and low side pressures are equalized. The revised procedure introduces a second test condition that can possibly detect a leak (or leaks) that the first test condition could not.
The service manuals listed below will contain the updated leak detection procedures:
- 1997 I30
- 1998 J30
- 1997 Q45
Please reference service procedures under Contents at the beginning of the HA section. Within this section refer to "Checking Refrigerant Leaks" to find the leak detection procedures.