Low Temperature Protection Control

WARNING: This page is about a different variant/trim than selected.

Unified meter and A/C amp. turns compressor ON or OFF as judged by a signal detected by ambient sensor and intake sensor.

When ambient temperature is higher than -2°C (28°F), the compressor turns ON. The compressor turns OFF when ambient temperature is lower than -5°C (23°F).

Fig 1: Ambient Temperature Graph
G04878036Courtesy of NISSAN NORTH AMERICA, INC.

When intake air temperature is higher than 1°C (34°F), the compressor turns ON. The compressor turns OFF when intake air temperature is lower than -5°C (23°F).

Fig 2: Intake Air Temperature Graph
G04878037Courtesy of NISSAN NORTH AMERICA, INC.