FixVault

Electrical Circuit Inspection Procedure

  1. Procedures for Open Circuit
    • Continuity Check
    • Voltage Check

    If an open circuit occurs (as seen in Fig 1), it can be found by performing Step 2 (Continuity Check Method) or Step  3 (Voltage Check Method) as shown below.

    Fig 1: Checking Open Circuit
    G12170334Courtesy of KIA MOTORS AMERICA, INC.
  2. Continuity Check Method
    NOTE: When measuring the resistance, lightly shake the wire harness up and down or from side to side.

    Specification (Resistance) 

    1Ω or less → Normal Circuit

    1MΩ or Higher → Open Circuit

    1. Disconnect connectors (A), (C) and measure resistance between connectors (A) and (C) as shown in [Fig 2].

      In Fig 2, the measured resistances of line 1 and 2 are higher than 1 MΩ and below 1 Ω respectively. Specifically, an open circuit is in line 1.

      (Line 2 is normal.) To find the exact broken point, check the sub line of line 1 as described in the next step.

      Fig 2: Measuring Resistance Between Connector (A) And (C)
      G12170335Courtesy of KIA MOTORS AMERICA, INC.
    2. Disconnect connector (B), and measure the resistance between connectors (C) and (B1) and between (B2) and (A) as shown in Fig 3.

    In this case the measured resistance between connector (C) and (B1) is higher than 1MΩ and the open circuit is between terminal 1 of connector (C) and terminal 1 of connector (B1).

    Fig 3: Measuring Resistance Between Connector (A) And (C)
    G12170336Courtesy of KIA MOTORS AMERICA, INC.
  3. Voltage Check Method
    1. With each connector still connected, measure the voltage between the chassis ground and terminal 1 of each connectors (A), (B) and (C) as shown in Fig 4.

      The measured voltages of each connector are 5V, 5V and 0V respectively. So, the open circuit is between connectors (C) and (B).

    2. Fig 4: Measuring Voltage Between Chassis Ground And Terminal 1 Of Each Connectors (A), (B) And (C)
      G12170337Courtesy of KIA MOTORS AMERICA, INC.