Room Temperature Sensor: Inspection
- REMOVE LOWER FINISH PANEL
- Remove the 3 screws.
- Release the 3 claws and pull out the lower finish panel.
- REMOVE ROOM TEMPERATURE SENSOR
- Disconnect the connector and aspirator hose.
- Release the 2 claws and pull out the sensor.
- INSPECT ROOM TEMPERATURE SENSOR RESISTANCE
Measure resistance between terminals at each temperature as shown in the chart.
TEMPERATURE SPECIFIED CONDITIONTemperature Specified condition 25°C (77°F) 1.6-1.8 kΩ 50°C (122°F) 0.6-0.8 kΩ If resistance is not as specified, replace the sensor.
- INSTALL ROOM TEMPERATURE SENSOR
- Install the sensor and fit the 2 claws.
- Connect the aspirator hose and connector.
- INSTALL LOWER FINISH PANEL
- Install the lower finish panel and fit the 3 claws.
- Install the 3 screws.