Blower Resistor: Inspection

  1. INSPECT BLOWER RESISTOR 
    1. Measure the resistance according to the value(s) in the table below.

      Standard resistance 

      RESISTANCE REFERENCE CHART

      Tester Connection Specified Condition
      1 - 2 1.398 to 1.605 Ω
      1 - 3 0.465 to 0.535 Ω
      1 - 4 3.069 to 3.531 Ω
      Fig 1: Identifying Blower Motor Connector Terminals
      G05195380Courtesy of © TOYOTA, LICENSE AGREEMENT TMS1002

      If the resistance is not as specified, replace the blower resistor.